Legionella control & water hygiene across the UK[email protected]
Compliance

ACoP L8 and HSG274 Explained: A Practical Guide for Duty Holders

ACoP L8 and HSG274 are the two documents that set the standard for legionella control in the UK. Here is what they say, in plain English.
8 min read · Updated October 2026

What is ACoP L8?

Legionnaires' disease: The control of legionella bacteria in water systems, known as ACoP L8, is HSE's Approved Code of Practice. The current fourth edition was published in 2013. It has special legal status: if you do not follow it, you must be able to show that you have complied with the law in another equally effective way.

What is HSG274?

HSG274 is HSE's technical guidance that sits alongside L8. It has three parts:

  • Part 1: evaporative cooling systems such as cooling towers
  • Part 2: hot and cold water systems, which covers most buildings
  • Part 3: other risk systems, including spa pools, humidifiers and vehicle washes

Duty holder and responsible person

The duty holder is the employer or person in control of the premises. They carry the legal responsibility. The duty holder should appoint a responsible person, someone with sufficient authority, competence and knowledge of the installation, to manage day-to-day control. That person may be supported by a competent contractor.

The written scheme of control

Where a risk is identified, you need a written scheme that explains how the risk is controlled. It should include an up-to-date schematic of the system, the control measures, the checks to be carried out and how often, and what to do if results go out of range.

Typical HSG274 Part 2 checks

TaskTypical frequency
Flush little-used outletsWeekly
Sentinel outlet temperaturesMonthly
Calorifier flow and return temperaturesMonthly
Clean and descale shower heads and hosesQuarterly, or as needed
Cold water tank temperature and conditionEvery six months to annually
Representative outlet temperatures on a rotational basisAnnually
TMV in-service checksAt least annually
Calorifier inspection and drainAnnually

Your own risk assessment may set different frequencies depending on the system and the people at risk.

Record keeping

Records should be kept for at least five years. That includes the risk assessment, the written scheme, monitoring and inspection results and details of remedial work. Our digital log books make this simple.

Frequently asked questions

Is ACoP L8 a law?

ACoP L8 is not law itself, but it has special legal status. Following it is usually enough to show compliance with the law on legionella.

How long should legionella records be kept?

At least five years.

Disclaimer: This guide is general information about UK requirements and is not legal advice. Always check the current legislation and guidance for your premises.