Water Temperature Log

A monthly record for sentinel outlet and calorifier temperatures, with the HSG274 targets printed on the sheet.

How to use this sheet

  1. List your sentinel outlets and hot water plant
  2. Hot outlets: record the temperature after one minute (target 50°C or more, 55°C in healthcare)
  3. Cold outlets: record the temperature after two minutes (target below 20°C)
  4. Calorifiers: flow 60°C or more, return 50°C or more
  5. Mark any reading outside the target and write down the action taken

Water Temperature LogAquastead Water · aquasteadwater.co.uk
Building
Date
Thermometer ID
Checked by
Outlet or plantHot / coldReading (°C)TargetPass?Action takenInitials

Keep completed records for at least five years. General guidance only: follow your own risk assessment where it sets different checks or frequencies.

Frequently asked questions

What are sentinel outlets?

The outlets nearest to and furthest from the hot water source or cold tank on each loop. They are checked monthly.

What if a temperature is out of range?

Investigate the cause, fix it, re-check and record what you did.